Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/30/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/26/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) RECEPTS MORE THAN 1/4" #4 PREVIOUS 2) SUB PANELS (BREAKER) FILL UNUSED OPENINGS, SECURE NM CABLES, VERIFY GROUNDING EQUIPMENT AND IDENTIFY UNINSULATED NEUTRAL (FUSE) SEPERATE GROUNDS AND NEUTRALS, VERIFY CONDUCTOR AMPACITY TO FUSE SIZE, MULTIPLE TERMINATIONS 3) OPEN EXPOSED CONDUCTORS BY WATER HEATER |
|
| 06/16/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : 1 - LIGHT ABOVE SERVICE NOT TO CODE 2 - MISSING WEATHER PROOF COVER ON RECEPTACLE BELOW PANEL 3 - PROPERLY SEAL ENTRANCES ABOVE CURRENT CARRING PARTS WITH AN APPROVED DEVICE AT SERVICE 4 - RECEPTACLES IN WALL MORE THAT 1/4" BOX TO SURFACE (UP TO 1" BACK) 5 - SMOKE DETECTOR NEEDED IN BEDROOM - INSTALL PER INSTRUCTIONS 6 - PROPERLY BLANK JUNCTION BOXES 7 - PROPERLY WIRE HOOD - A CONNECTOR IS ALSO NEEDED 8 - RECEPTACLE NOT ACCESSIBLE BELOW BACKSPLASH 9 - SUB PANEL NOT WIRED TO CODE 10 - VERIFY PERMITS FOR ADDITION 11 - VERIFY PERMITS FOR WATER HEATER - COMBUSTION RELIEF & PRESSURE RELIEF |