Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/14/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/10/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) CONDUIT AT SERVICE SUPPORTS NOW SEPERATING FROM STRUCTURE 2) FINISH #1, 3 & 5 |
|
| 06/15/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ADDRESS SERVICE AND DISCONNECTS SUITE #100, POST SUITE AND ADDRESS ON UNITS 2) REATTACH BOND CLAMP 3) VERIFY GROUNDING ELECTRODE SYSTEM SERVICE #100 4) OPEN JUNCTION 5) SECURELY ATTACH BUSS DUCTS TO BLDG-OPEN HOLE TAP BOX OPEN ENDS 6) MAINTAIN WORKING CLEARANCE AT SUB PANEL 7) CORRECTLY SUPPORT SEAL TITE FROM SUB PANEL 8) OPEN CORD HANGING OUT OF SUB PANEL 9) OPEN JUNCTION BOXES 10) CORD HANGING RECEPTS NOT ALLOWED 11) SUPPORT CONDUITS AS PER CODES-USE APPROVED CONDUIT 12) WIRING IN STUD FRAME WALL NOT TO CODES 13) HAVE QUALIFIED ELECTRICIAN PERFORM WORK |