Permit: T10EL01413

Parcel: 12904226C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T10EL01413

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/14/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/10/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) CONDUIT AT SERVICE SUPPORTS NOW SEPERATING FROM STRUCTURE
2) FINISH #1, 3 & 5
06/15/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ADDRESS SERVICE AND DISCONNECTS SUITE #100, POST SUITE AND ADDRESS ON UNITS
2) REATTACH BOND CLAMP
3) VERIFY GROUNDING ELECTRODE SYSTEM SERVICE #100
4) OPEN JUNCTION
5) SECURELY ATTACH BUSS DUCTS TO BLDG-OPEN HOLE TAP BOX OPEN ENDS
6) MAINTAIN WORKING CLEARANCE AT SUB PANEL
7) CORRECTLY SUPPORT SEAL TITE FROM SUB PANEL
8) OPEN CORD HANGING OUT OF SUB PANEL
9) OPEN JUNCTION BOXES
10) CORD HANGING RECEPTS NOT ALLOWED
11) SUPPORT CONDUITS AS PER CODES-USE APPROVED CONDUIT
12) WIRING IN STUD FRAME WALL NOT TO CODES
13) HAVE QUALIFIED ELECTRICIAN PERFORM WORK