Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/18/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/16/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/11/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BATHROOM RECEPTS TO BE GFCI PROTECTED 2) PROTECT NM CABLE TO LIGHT FIXTURE STORE ROOM 3) MULTI-POLE CONDUCTOR TERMINATIONS AT MAIN DISCONNECTS 4) RE-DO ALUMNIUM TERMINATIONS-TIGHTENING AND ANTIOXIDE COMPOUND 5) SUB PANELS NOT WIRED TO CODE 6) THIS IS AN OLD MEDICAL FACILITY WITH PATIENT CARE AREAS OF 517 WIRING NOT MEETING REQUIREMENTS 7) OTHER VIOLATIONS PRESENT, HAVE QUALIFIED ELECTRICIAN GO THRU AND PERFORM WORK |