Permit: T10EL01401

Parcel: 117072140


Addresses:

705 S 6TH AV


Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Permit Number - T10EL01401

Inspection Description - ELECTRIC - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
07/01/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 1 AND 4 STILL HAVE ISSUES ON LIST
06/25/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) A LISTED MAST BRACE KIT IS NEEDED
2) SUPPORT CONDUIT ON SIDE OF PANEL WITHIN 3' OF LB
3) MISSING BOTTOM LB COVER
4) VERIFY DERATING OF NM CABLE THRU RACEWAY-12 CONDUCTORS 310.15
2) ENERGIZED WITHOUT CLEARANCE