Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10EL01389
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/17/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/16/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. NEED SMOKE DETECTORS IN BEDROOMS 2. EXPOSED WIRES IN LOFT CEILING 3. REPAIRED WIRING AT COUNTER BY REAR DOOR NEEDS TO BE IN JUNCTION BOX 4. KITCHEN COUNTER AND BATHROOM OUTLETS NEED TO BE GFCI PROTECTED. 5. LABEL BREAKRES CORRECTLY, ONLY 1 GFCI IN BATHROOM 6. TERMINATE DISHWASHER AND A/C WIRING CORRECTLY |
|
06/14/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : CALLED 975-2293, GOT NO RETURN CALL NO ACCESS TO LOCK BOXES, |