Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10EL01372
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/15/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/09/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/14/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : 1 - MAINTAIN WORKING SPACE IN FRONT OF ELECTRICAL SERVICE 2 - CANNOT EXIT THROUGH TOP END WALL PER INSTRUCTIONS 3 - SECURE & BURY BOND CONDUCTOR 4 - PROVIDE LADDER TO OPEN JUNCTION BOX TO INSPECT 5 - CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS 6 - BREAKER TO BE SIZED FOR AMPACITY OF NM CABLE 334.80 7 - PLEASE VERIFY PERMIT FOR NEW WIRING - NM CABLE DATE 7-11-09 8 - PLEASE VERIFY PERMIT FOR NEW A/C UNIT |