Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T10EL01372
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2010 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 07/09/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PERMIT FOR NEW WORK STILL IN APPLIED STATUS 2) NO LOADS CONNECTED AT THIS TIME 3) GAS AND WATER BONDS WILL NEED TO BE TO NEW PANEL AND BURY CONDUCTOR 4) BREAKERS TO E LISTED FOR USE BY MANUFACTURE 5) PROVIDE A SAFE LADDER 6) RISER SUPPORTING HARDWARE TO BE 1/4" MINIMUM |
|
| 06/14/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : 1 - MAINTAIN WORKING SPACE IN FRONT OF ELECTRICAL SERVICE 2 - CANNOT EXIT THROUGH TOP END WALL PER INSTRUCTIONS 3 - SECURE & BURY BOND CONDUCTOR 4 - PROVIDE LADDER TO OPEN JUNCTION BOX TO INSPECT 5 - CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS 6 - BREAKER TO BE SIZED FOR AMPACITY OF NM CABLE 334.80 7 - PLEASE VERIFY PERMIT FOR NEW WIRING - NM CABLE DATE 7-11-09 8 - PLEASE VERIFY PERMIT FOR NEW A/C UNIT |