Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T10EL01341

Parcel: 129053030


Addresses:

2250 E 18TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
06/10/2010 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
06/09/2010 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) USE APPROVED FITTING WITH LB ON SIDE OF PANEL AND SEAL WITH APPROVED PARTS
2) SUPPORT RISER BELOW ROOF
3) FILL UNUSED OPENINGS IN JUNCTION BOX AND TIGHTEN FITTING
4) PLEASE VERIFY 2ND GROUNDED AND GAS PIPING
5) SECURE GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE
6) LABEL BREAKERS