Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/19/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH #1 & #7 PREVIOUS INSPECTION |
|
| 06/08/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LIGHT AT SHELVES TO BE PER 410.8 2) CONDUIT ON EXTERIOR OF UNIT NOT INSTALLED FOR WET LOCATION OR PROPERLY SUPPORTED 3) WATER HATER NOT CORD AND PLUG APPLIANCE 4) CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS 5) USE CORRECT SIZED BREAKERS FOR CONDUCTOR AMPACITY 6) NEED ANTIOXIDE COMPOUND FOR ALUMINUM CONDUCTORS 7) USE BREAKERS LISTED FOR USE BY MANUFACTURE 8) ONLY ONE CONDUCTOR TERMINATION PER LUG 9) NEED PERMANENT METAL ADDRESS LABEL ON SERVICE 10) FINISH 100 PERCENT BEFORE NEXT INSPECTION-A REFEE MAYBE ASSESED 11) PLEASE VERIFY QUALIFIED ELECTRICIAN |