Permit: T10EL01321

Parcel: 137273130

Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/09/2010 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
07/09/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/07/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
1) NEED SMOKE DETECTORS IN BEDROOMS
2) MISSING KITCHEN OUTLET/RECEPT 210.52
3) KITCHEN RECEPTS TO BE GFCI PROTECTED 210.8
4) FOLLOW HANOUT SHEET
5) PLEASE PAY REFEE BEFORE NEXT INSPECTION PER ADMIN. CODES
06/28/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FINISH PREVIOUS ITEMS AND VERIFY WHO QUALIFIED ELECTRICIAN IS ?
06/03/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REPAIR PANEL COVER
2) MAIN BREAKER NOT ATTACHED TO BUSS
3) PROPERLY IDENTIFY UNGROUNDED CONDUCTORS
4) SEAL ENTRANCES ABOVE PANEL WITH APPROVED DEVICE
5) BREAKER TO BE LISTED FOR USE BY MANUFACTURE
6) OPEN WIRING AT OLDE POLL EQUIPMENT
7) IMPROPER WIRING REAR PORCH
8) MISSING LIGHT FIXTURES GARAGE
9) FRONT GARAGE LIGHT IMPROPERLY INSTALLED
10) INSPECTION STOPPED-INTERIOR OF UNIT IS NOT HABITABLE-HAVE QUALIFIED CONTRACTORS TO BRING HOUSE INTO HABITABLE STATE-PLUMBING, MECHANICAL AND ELECTRICAL PERMITS WILL BE NEEDED FOR FURNACE AND WATER HEATER (MISSING)