Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/16/2010 | ELECTRIC - FINAL | Approved | ||
| 07/14/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio |
|
| 07/09/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) IMPROPER WIRING METHODS AT RECEPT IN BATHROOM 2) BULB AND GLOBE MISSING IN LAUNDRY ROOM 3) LIGHT FIXTURE IN BATHROOM NOT INSTALLED 4) PROVIDE A PERMIT FOR THE BATHROOM REMODEL PRIOR TO RELEASE OF ELECTRIC CLEARANCE |
|
| 07/08/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CANNOT USE A WATER PIPE FOR EQUIPMENT GROUND FOR RECEPTACLE IN BATHROOM 2) ALL NEW ELECTRICAL AND PLUMBING WORK REQUIRED TO HAVE A PERMIT (BATHROOM REMODEL) 3) BATHROOM EXHAUST MISSING COVER 4) PROVIDE A LIGHT BULB AND GLOBE IN LAUNDRY ROOM 5) COVER PLATE MISSING AT WATER HEATER IN GUEST HOUSE 6) ALSO WATER HEATER MISSING COVER PLATE FOR CONTROL WIRING 7) COVER PLATE MISSING AT RECEPT IN FAMILY ROOM GUEST HOUSE 8) 5 POUND OUTSIDE GUEST HOUSE MISSING COVER PLATE 9) SUB PANEL MISSIING COVER PLATE |