Permit: T10EL01294

Parcel: 135043020

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/11/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/10/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LABEL ALL BREAKERS
2) CONNECT EQUIPMENT GROUND TO JUNCTION BOX
3) EQUIPMENT GROUND TO BE SIZED BY LARGEST CIRCUIT IN RACEWAY. HAVE CWA FEED IN RACEWAY GROUND TO BE #10
4) NEED TO INSTALL LOCK NUT ON OTHER SIDE OF CHASE NIPPLES FOR GOOD METAL TO METAL CONTACT
5) IF USING REDUCING WASHERS NEED TO BE INSTALLED PER INSTRUCTIONS FOR PROPER BONDING OR INSTALL BONDING BUSHING