Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/14/2010 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 06/11/2010 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1) SERVICE EQUIPMENT TO HIGH OFF GRADE 6' 7" MAX TO HIGHEST BREAKER 2) GROUNDS AND LOADS NOT CONNECTED YET 3) GROUND RODS MUST BE FLUSH WITH GRADE. BOND WATER/GAS PIPING 4) SUPPORT RISER BELOW ROOF OVERHANG |