Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/03/2010 | ELECTRIC - FINAL | Approved | ||
| 05/27/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED PROPER WORKING CLEARANCE IN FRONT OF ELECTRIC EQUIPMENT AT OFFICE TRAILER. MINIMUM CLEARANCE IS 36" HAVE ONLY 24". NEED TO MOVE TRAILER OR ELECTRIC TO HAVE PROPER CLEARANCE. CITY REQUIRED 12 FOOT FIRE WALL TO BUILT ON PROPERTY LINE SO NOW PROPER CLEARANCE IS NO LONGER AVAILABLE. CAN ALSO CONTACT LEE RAY HANLY 909-5154 TO APPEAL WORKING CLEARANCES 2) ALL OTHER ITEMS HAVE BEEN CORRECTED |
|
| 05/21/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING DEAD FRONT ON PANEL 2) SEAL OPEN KNOCKOUTS 3) INSTALL GROUNDING ELECTRODE SYSTEM AT OUT BLDG BOND PIPING SYSTEMS 4) DAMAGED AND HAZARDOUS WIRIGN THROUGHOUT PROPERTY 5) OUTDOOR RECEPTS TO BE GFI PROTECTED AND BE WEATHERPROOF 6) INSTALL GROUNDING ELECTRODE SYSTEM AND BOND PIPING SYSTEMS AT OFFICE BLDG 7) NEED PROPER WORKING CLEARANCES IN FRONT OF ELECTTRIC PANELS AT OFFICE BLDG. HAVE NEW CMU WALL APPROX. 12' TALL 8) SERVICE PANELS LOCKED 9) NEED ACCESS TO BLDG 10) TO MANY HAZARDS TO LIST, NEED TO OBTAIN SERVICES OF ELECTRICAL CONTRACTOR TO GO THRU ENTIRE PROPERTY AND MAKE CORRECTIONS AS NEEDED |