Permit: T10EL01186

Parcel: 130152330


Addresses:

4685 E 26TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/21/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/19/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* SMOKE DETECTORS TO BE MIN 36" FROM HEATING DIFFUSER.
07/14/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
07/09/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED ACCESS TO INTERIOR OF HOME
2) USE LOCK NUT AT CHASE NIPPLE CONNECTION TO PANEL FOR GOOD METAL TO METAL CONTACT
3) USE WIRE NUTS OR CRIMPS AT EQUIPMENT GROUND SPLICES
4) EQUIPMENT GROUND TO BE CONNECTED TO JUNCTION BOX THAT CONTAINS SPLICES
05/19/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) OUTDOOR RECEPTS TO BE GFI PROTECTED
2) BROKEN FIXTURE IN STORAGE
3) FLOOD LIGHT AT CARPORT TO BE INSTALLED ON WEATHERPROOF BOX
4) GO THRU RECONNECT SHEET REQUIREMENTS LEFT ON SITE
5) MISSING WALL PLATES
6) OUTDOOR ELECTRIC ON REAR OF HOME IS HAZARDOUS
7) SERVICE TO HOME IN HAZARDOUS CONDITIONS AND NEEDS TO BE REPLACED, EXSITING PANEL IS FOR INDOOR USE ONLY AND SERVICE DROP HAS PULLED STRIKE KNOBS OUT OF ROOF
8) OBTAIN SERVICES OF ELECTRICAL CONTRACTOR TO MAKE REPAIRS