Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/19/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SMOKE DETECTORS TO BE MIN 36" FROM HEATING DIFFUSER. |
|
| 07/14/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio |
|
| 07/09/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED ACCESS TO INTERIOR OF HOME 2) USE LOCK NUT AT CHASE NIPPLE CONNECTION TO PANEL FOR GOOD METAL TO METAL CONTACT 3) USE WIRE NUTS OR CRIMPS AT EQUIPMENT GROUND SPLICES 4) EQUIPMENT GROUND TO BE CONNECTED TO JUNCTION BOX THAT CONTAINS SPLICES |
|
| 05/19/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) OUTDOOR RECEPTS TO BE GFI PROTECTED 2) BROKEN FIXTURE IN STORAGE 3) FLOOD LIGHT AT CARPORT TO BE INSTALLED ON WEATHERPROOF BOX 4) GO THRU RECONNECT SHEET REQUIREMENTS LEFT ON SITE 5) MISSING WALL PLATES 6) OUTDOOR ELECTRIC ON REAR OF HOME IS HAZARDOUS 7) SERVICE TO HOME IN HAZARDOUS CONDITIONS AND NEEDS TO BE REPLACED, EXSITING PANEL IS FOR INDOOR USE ONLY AND SERVICE DROP HAS PULLED STRIKE KNOBS OUT OF ROOF 8) OBTAIN SERVICES OF ELECTRICAL CONTRACTOR TO MAKE REPAIRS |