Permit: T10EL01185

Parcel: 130121520


Addresses:

3714 E SHEPHERD PL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/13/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/19/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SUPPORT CONDUITS AROUND HOUSE ON EXTERIOR & TIGHTEN
2) USE APPROVED JUNCTION BOX COVERS NOT HOME MADE
3) SMOKE DETECTORS NEEDED FOR BEDROOMS AND HALL-INSTALL PER INSTRUCTIONS
4) GROUNDED RECEPTS ON NON GROUNDED CIRCUITS
5) WROUGHT IRON IN BEDROOMS TO HAVE QUICK RELEASE-REMOVED
6) MISSING JUNCTION BOX COVERS-BOXES TO BE ACCESSIBLE
7) KITCHEN RECEPTS TO BE GFCI PROTECTED
8) RECEPTS NOT ATTACHED TO BOXES-ALSO WHERE DRYWALL HAS BEEN ADDED BOXES MORE THAN 1/4" BOX TO SURFACE 314.20
9) FILL UNUSED OPENINGS IN PANELS
10) WHERE IS OVER CURRENT PROTECTION FOR 30A + 50A RECEPTS