Permit: T10EL01173

Parcel: 141192940

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/06/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/15/2010 ELECTRIC - FINAL Denied 1) KITCHEN OUTLETS TO BE GFI'S ON COUNTER
2) SMOKE DETECTOR MISSING IN FIRST BEDROOM
3) GARAGE OUTLET BY DOOR TO BE GFI AND MISSING COVER PLATE
4) UPSTAIRS BEDROOM MISSING OUTLET COVER PLATE
06/09/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 1" EMT INSTALLED FROM SERVICE PANEL TO 2ND FLOOR NOT INSTALLED PER CODE. INSTALL PER CODE OR REMOVE
2) HAVE #12 AWG WIRE BEING PROTECTED BY 30 AMP BREAKER
3) INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL
4) STRAP SEAL TIGHT AT PANEL
5) INSTALL MISSING SCREWS FOR PANEL COVERS
6) REPLACE BROKEN WEATHERPROOF COVERS
7) WIRING IN BACKYARD NOT INSTALLED PER CODE. RACEWAYS DAMAGED/? CABLE EXPOSED TO DAMAGE, RECEPT TO BE GFI PROTECTED
8) LIGHT FIXTURE AT BACK DOOR BROKEN
9) THIS LIST IS FOR OUTDOOR ONLY AND NOT COMPLETE. LOCK BOX CODE WOULD NOT OPEN BOX. HAVE ELECTRICAL CONTRACTOR GO THRU PROPERTY & CHECK WIRING INSIDE AND OUT