Permit: T10EL01171

Parcel: 107120310


Addresses:

442 E BLACKLIDGE DR

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/27/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INCORRECT WIRING METHOD TO BACK ENTRY LIGHT FIXTURE
2) USE QUALIFIED ELECTRICIAN
3) A REINSPECTION FEE WILL BE ASSESED NEXT INSPECTION IF NOT CORRECT
06/28/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) STILL HAVE HAZARDOUS WIRING AND RECALL INSPECTIONS
2) CALLED AND LEFT MESSAGE PER REQUEST, NO ONE HOME
06/25/2010 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) SCHEDULE BOTH E2 PERMITS FOR INSPECTION AT SAME TIME
05/21/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GROUNDING ELECTRODE CONDUCTOR CUT OFF AT SERVICE EQUIP. REPAIR ASAP-LIFE SAFETY ISSUE
2) DEAD FRONT COVER MISSING AT AT SERVICE SUB PANEL
3) ISOLATE GROUNDS AND NEUTRALS AT BOTH SUB PANELS
4) CANNOT USE CHASE NIPPELA LB TERMINATION, SUPPORT EMT PER CODE 3 & 10 USE ROOF JACK
5) CANNOT SHARE NEUTRAL WHEN USING TWIN BREAKERS MULTI BRANCH CKTS IN SUB PANEL AT UNIT. GROUND (EQUIP) MUST BE CONTINOUS GREEN INSULATION
6) USE LICENSED CONTRACTOR OR QUALIFIED ELECTRICIAN TO DO WORK