Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/02/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/25/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GARAGE RECEPTS TO BE GFI PROTECTED PER 2005 NEC 210.8 (A) (2) 2) ROMEX CABLES ENTERING EMT NEED TO BE PROTECTED FROM PHYSICAL DAMAGE 2005 NEC 300.15 (C) 3) VERIFY #14 AWG WIRE IS ON 15 AMP CIRCUIT AND #12 AWG WIRE ON 20 AMP |