Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/21/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) THERE WAS A PERMIT FOR ENCLOSED PART GARAGE FOR ROOM" T97CM00903 APPROVED AND FINALED BY ROB FREIDINGER 4/18/97 |
|
| 06/10/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WIRING IN SHED IS HAZARDOUS. NEED TO BE INSTALLED PER CODE OR REMOVED 2) RECPTS IN SHED AND OUTSIDE SHED TO BE GFI PROTECTED 3) WIRING TO CEILING FAN AT PATIO IS HAZARDOUS AND NOT TO CODE 4) WIRING IN GARAGE/STORAGE NOT TO CODE, HAVE OPEN BOXES AND IMPROPER CONNECTIONS. JUNCTION BOX NOT ACCESSIBLE 5) IT APPEARS BEDROOM ADDITION IN GARAGE DONE WITHOUT PERMITS. REAL ESTATE LISTING HAS TOWNHOME WITH ONE BEDROOM. CANNOT HAVE BEDROOM NEXT TO GARAGE PER CODE |