Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/10/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/30/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 08/23/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 07/21/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) BOND BUSHING REQUIRED PER 250.92 NEC SUPPLY SIDE OF SERVICE EQUIP OK 2) SERVICE DISCONNECT ARE NOT RATED FOR OUTDOOR USE. THIS SHOULD BE A COMPLEE SERVICE UPGRADE. SOME WATER HAS BEEN ENTERING AND CAUSING RUST, ALSO EXPOSED ROMEX BELOW UNIT #1 DISC. SW NEEDS TO BE IN RACEWAY. PLEASE ADDRESS THESE ITEMS. FAILURE WILL RESULT IN CASE HANDED OVER TO DNR-CITY OF TUCSON |