Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/25/2010 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 05/14/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) OK GROUND RODS 2) OK GAS AND WATER BOND 3) NEED PANEL DIRECTORY 4) SIZE EQUIPMENT GROUNDS PER 250.122 5) IDENTIFY EQUIPMENT GROUNDS PER 250.119 6) CANNOT USE OLD PANEL BOX AS JUCTION BOX 7) CANNOT SPLICE ALUMINUM AND COPPER CONDUCTORS TOGETHER 8) PROTECT CABLES AND ENTRY TO ENCLOSURES WITH CONNECTORS OR BUSHING 9) STRAP EMT WITHIN 3' OF CONNECTIONS 10) SERVICE ENERGIZED WITHOUT APPROVAL |