Permit: T10EL01042

Parcel: 122180330


Addresses:

1630 N WINSTEL BL

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/19/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) #1 & 2 ON LIST STILL HAVE TO BE CORRECTED
05/12/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) IN GUTTER BOX ON NORTH WALL SPLIT BOLT CANNOT HAVE 5 WIRES
2) ON BOTTOM AND BACK OF PANEL COVER UP OPENINGS
3) SCREWS ON HINGE ARE TO LONG, 1 SCREW MISSING ON DEAD FRONT
4) ARE SERVICE WIRES THE RIGHT SIZE, SUN RESISTANT AND HAVE LADDER ON NEXT INSPECTION
5) CLEAN SHAVINGS IN GUTTER
6) BOND BUSHING NEEDED ON CONCENTRIC KNOCKOUTS, 1 1/4 EMT UNDER PANEL/250.97