Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/07/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/04/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) MAINTAIN WIRE BENDING RADIUS FOR CONDUCTOR-NEUTRAL 312.6 |
|
| 05/21/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SERVICE ENERGIZED WITHOUT APPROVAL, NEED TO OPEN METER SECTION OF SERVICE 2) DRIVE GROUND RODS BELOW GRADE 3) INSTALL LISTED MAST BRACING 4) CONDUCTORS NOT SIZED PROPERLY FOR 100 AMP FEED TO SUB PANEL. THIS IS NOT MAIN POWER FEEDER 370.15 (B) (6) DOES NOT APPLY 5) CLEANOUT DEBRIS FROM PANELS |