Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/11/2010 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) OK GROUND RODS, NEED TO COMPLETELY DRIVE & BURY GROUND WIRE 2) NEED TO BOND GAS AND WATER PIPING SYSTEMS 3) OBTAIN PERMIT FOR NEW ROOF TOP UNIT. PROVIDE COPY AT NEXT INSPECTION 4) RECALL WHEN SWING OVER COMPLETE |