Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/14/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 06/10/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) VERIFY IF WE HAVE 2 CIRCUITS FOR KITCHEN PER CODE OR ONE #3 2) FINISH GAS PACK WIRING TO CODE #7 3) VERIFY PERMITS #9 4) A REFEE MAY BE ASSESED |
|
| 05/03/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) POST ADDRESS ON BLDG 2) BATHROOM RECEPTS TO BE GFCI PROTECTED 3) KITCHEN RECEPTS TO BE GFCI PROTECTED 4) MISSING COVER PLATES 5) SMOKE DETECTORS NEEDED IN BEDROOMS-INSTALL PER INSTRUCTIONS 6) EXTERIOR WIRING NOT TO CODE 7) AAS PACK WIRING NOT TO CODE 8) FILL UNUSED OPENINGS IN DEAD FRONT 9) PLEASE VERIFY PERMITS FOR ADDITION TO CARPORT AND WALLS ON INTERIOR 10) SHED WIRING NOT TO CODE |