Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/10/2010 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 05/06/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) EXPOSED CONDUCTORS ON EXTERIOR AND INTERIOR OF STRUCTURE 2) BOND JUNCTION BOX ENCLOSURE 3) PROPERLY IDENTIFY GROUNDED CONDUCTOR 4) CANNOT USE GROUNDED CONDUCTOR FOR BONDING 5) BRACE SUPPORTS TO BE INTO JOIST MEMBERS NOT PLY WOOD ROOF ONLY 6) CLEAN PAINT SURFACE UNDER BOND CLAMPS-GAS AND WATER 7) SERVICE ENTRANCE CONDUCTOR TO BE MARKED "SUN LIGHT RESISTANT" 8) OBSERVATION THRU WINDOW NOTE INTERIOR MAY HAVE ELECTRICAL VIOLATIONS TO BE ADDRESSED BY ELECTRICIAN |