Permit: T10EL00974

Parcel: 118031590

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/18/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/27/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) SUPPORT CONDUIT ON SIDE OF PANEL
2) SEAL ENTRANCE ABOVE CURRENT CARRING PART WITH AN APPROVED DEVICE
3) USE APPROVED AND LISTED REDUCING WASHERS
4) NEED BOND BUSHING ON SERVICE NIPPLE