Permit: T10EL00943

Parcel: 10605070A

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
05/11/2010 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
05/05/2010 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/28/2010 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) USE APPROVED W/P HUB OR SEALING LOCKNUT FOR TOP PENETRATION
2) CIRCUIT BREAKERS MUST BE SAME BRAND AS SERVICE PANEL 110.3
3) WATER FAUCET CANNOT BE IN FRONT OF SERVICE PANEL 110.26
4) EXPOSED GROUND RODS
5) TWIN CIRCUIT BREAKERS CANNOT SHARE NEUTRAL
6) WATER AND GAS PIPE BONDING ??
7) SERVICE RE-ENERGIZE PRIOR TO INSPECTORS APPROVAL