Permit: T10EL00926

Parcel: 138100270


Addresses:

5849 S 6TH AV #02

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/01/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) VERIFY GAS AND WATER BONDS
2) STRAP GROUND CONDUCTOR TO BLDG
3) LABEL BREAKERS
08/27/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) A SERVICE UPGRADE PERMIT WILL HAVE TO BE OBTAINED
08/23/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED AN APPROVED DEAD FRONT COVER
2) OUTDOOR RECEPT TO BE FOR WET LOCATION
3) BREAKER AND CONDUCTORS IN PANEL IN WEATHER DETIORATED CONDITION-NEEDS REPLACEMENT
4) FILL UNUSED OPENING IN PANEL
5) GROUNDED RECEPTS ON NON GROUNDED CIRCUITS
6) PROTECT BULB IN CLOSET
7) OBTAIN THE SERVICES OF A QUALIFIED ELECTRICIAN TO PERFORM WORK
8) POST ADDRESS ON BLDG