Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
Permit Number - T10EL00926
Inspection Description - ELECTRIC - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/01/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) VERIFY GAS AND WATER BONDS 2) STRAP GROUND CONDUCTOR TO BLDG 3) LABEL BREAKERS |
|
08/27/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) A SERVICE UPGRADE PERMIT WILL HAVE TO BE OBTAINED |
|
08/23/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED AN APPROVED DEAD FRONT COVER 2) OUTDOOR RECEPT TO BE FOR WET LOCATION 3) BREAKER AND CONDUCTORS IN PANEL IN WEATHER DETIORATED CONDITION-NEEDS REPLACEMENT 4) FILL UNUSED OPENING IN PANEL 5) GROUNDED RECEPTS ON NON GROUNDED CIRCUITS 6) PROTECT BULB IN CLOSET 7) OBTAIN THE SERVICES OF A QUALIFIED ELECTRICIAN TO PERFORM WORK 8) POST ADDRESS ON BLDG |