Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/29/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED |
|
| 08/05/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) NO WORK PROGRESS-A REFEE MAYBE ASSESED |
|
| 07/07/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) GROUNDING EQUIPMENT CONDUCTOR TO BE SIZED PER 250.122 |
|
| 07/02/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED |
|
| 06/17/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : 1- OLD ALL IN ONE NOT ALLOWED FOR JUNCTION BOX/SUB PANEL LISTED AS SERVICE EQUIPMENT ONLY 2 - CORRECTLY IDENTIFY UNGROUNDED CONDUCTOR - COLORS TO BE CONTINUOUS IN RACEWAY SYSTEM 3 - NEED CORRECT BREAKER SIZE PER SECTION 334.80 FOR NM CABLE 4 - DERATED CONDUCTORS PER SECTION 310.15 |
|
| 06/08/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) RECALL AFTER CROSSOVER 2) NOTE: 680.8 MAY APPLY |