Permit: T10EL00882

Parcel: 136383890

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/11/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/22/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HAVE FLOATING GROUNDS IN PANEL
04/15/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EXPOSE GROUND RODS
2) GROUNDING ELECTRODE CONDUCTOR TO TERMINATE ON NEUTRAL BAR
3) CANNOT USE SHEET METAL SCREW FOR CONNECTION OF GROUNDS TO PANEL
4) BOND NIPPLE INTO PANEL FROM METER
5) MARK ALL CIRCUITS
6) SECURE RECEPT BOX UNDER PANEL
7) BOND PIPING SYSTEMS