| 05/11/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/22/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) HAVE FLOATING GROUNDS IN PANEL |
|
| 04/15/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXPOSE GROUND RODS 2) GROUNDING ELECTRODE CONDUCTOR TO TERMINATE ON NEUTRAL BAR 3) CANNOT USE SHEET METAL SCREW FOR CONNECTION OF GROUNDS TO PANEL 4) BOND NIPPLE INTO PANEL FROM METER 5) MARK ALL CIRCUITS 6) SECURE RECEPT BOX UNDER PANEL 7) BOND PIPING SYSTEMS |