Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/19/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 04/16/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO BOND BOTH ENDS OF RACEWAY 250.64 E 2) NEED GROUND RODS BELOW GRADE 250.33 G |
|
| 04/14/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED GROUNDING AT SERVICE 2) NEED GROUNDING LUG AT SUB PANEL |