Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/09/2010 | ELECTRIC - RECONNECT | Partial Approval | IVRS - Inspection :* | |
| 07/08/2010 | ELECTRIC - RECONNECT | Not ready for Inspection | ||
| 04/12/2010 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) VERIFY GROUNDING OF SERVICE INTACT, SHOULD HAVE 2 GROUND RODS, WATER AND GAS PIPES BONDED 2) OBTAIN PLANS/PERMIT FOR NEW WIRING IN KITCHEN, USE NAIL PLATES WHERE CABLE IS LESS THAN 1 1/4" FROM STUD FACE TO PROTECT FROM NAILS AND SCREWS 3) FILL UNUSED OPENINGS IN SERVICE PANEL 4) SECURITY LIGHT NOT WIRED PER CODE 5) EXPOSED ROMEX IN STORAGE ROOMO OUTSIDE 6) INSTALL SMOKE DETECTORS IN HALLWAY AND BEDROOMS 7) INSTALL GFI PROTECTED RECEPTS IN BATHROOMS AND KITCHEN COUNTERS 8) DO NOT COVER WALLS IN KITCHEN UNTIL PROPER PERMIT, APPROVED PLANS AND INSPECTIONS APPROVED FOR WORK 9) PROVIDE LADDER FOR ROOF INSPECTION 10) OBTAIN THE SERVICE OF A LICENSED OR QUALIFIED ELECTRICIAN |