Permit: T10EL00824

Parcel: 115220740


Addresses:

1532 N HUALPAI RD

Inspection Status: Partial Approval

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
08/09/2010 ELECTRIC - RECONNECT Partial Approval IVRS - Inspection :*
07/08/2010 ELECTRIC - RECONNECT Not ready for Inspection
04/12/2010 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) VERIFY GROUNDING OF SERVICE INTACT, SHOULD HAVE 2 GROUND RODS, WATER AND GAS PIPES BONDED
2) OBTAIN PLANS/PERMIT FOR NEW WIRING IN KITCHEN, USE NAIL PLATES WHERE CABLE IS LESS THAN 1 1/4" FROM STUD FACE TO PROTECT FROM NAILS AND SCREWS
3) FILL UNUSED OPENINGS IN SERVICE PANEL
4) SECURITY LIGHT NOT WIRED PER CODE
5) EXPOSED ROMEX IN STORAGE ROOMO OUTSIDE
6) INSTALL SMOKE DETECTORS IN HALLWAY AND BEDROOMS
7) INSTALL GFI PROTECTED RECEPTS IN BATHROOMS AND KITCHEN COUNTERS
8) DO NOT COVER WALLS IN KITCHEN UNTIL PROPER PERMIT, APPROVED PLANS AND INSPECTIONS APPROVED FOR WORK
9) PROVIDE LADDER FOR ROOF INSPECTION
10) OBTAIN THE SERVICE OF A LICENSED OR QUALIFIED ELECTRICIAN