Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/10/2010 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 05/03/2010 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
| 04/28/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SEAL ENTRANCE ABOVE CURRENT CARRING PARTS 2) MOVE GAS BOND TO INTERIOR SIDE PIPING 3) DERATE CONDUCTORS PER 310.15 AND 310.16 FOR HEAT 4) SUPPORT CONDUIT 3' FROM BOX 5) GROUND JUNCTION BOX AND FINISH MAKE UP |