Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/24/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/09/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL DEAD FRONT ON PANEL 2) SEAL OPEN KNOCKOUT AT PANEL 3) INSTALL BREAKERS LISTED FOR USE IN PANEL 4) INSTALL SMOKE DETECTORS IN BEDROOMS 5) OUTDOOR RECEPTS TO BE GFI PROTECTED AND HAVE WEATHER PROOF COVERS 6) CLOSE OPEN KNOCKOUTS IN JUNCTION BOXES 7) RESCHEDULE WHEN 100 PERCENT COMPLETE |