Permit: T10EL00764

Parcel: 126190350


Addresses:

4309 E MONTECITO ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
04/08/2010 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
04/07/2010 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WATER BOND TO BE #4 NEL 250.104
2) SEAL OPENING @ WIRE ENTRY WITH NON-COMBUSTIBLE MATERIAL
3) PROVIDE DETAILED PANEL SCHEDULE
4) IF POWER HAS BEEN OFF FOR MORE THAN 6 MONTHS NEED TO ADD RECONNECT INSPECTION TO PERMIT & PROVIDE ACCESS TO INTERIOR OF HOME.