Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/07/2010 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 06/03/2010 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) A SEALING LOCK NUT IS NEEDED TO SEAL ENTRANCE AT TOP OF PANEL 2) INSTALL ALL STRANDS UNDER BREAKER TERMINATION 3) CLEAN SURFACE UNDER GROUND BAR IN JUNCTION BOX 250.12 |
|