Permit: T10EL00746

Parcel: 136286460


Addresses:

4400 S DOGWOOD AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/15/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/14/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) STILL MISSING MAIN BONDING JUMPER
04/12/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PREVIOUS INSPECTION REPORT TO BE ON SITE
2) TEP ON SITE MARKING UNDERGROUND FOR NEW SERVICE TO HOME, NEED TO EXPLAIN
04/09/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL GROUND RODS
2) INSTALL BREAKERS LISTED FOR USE IN PANEL
3) INSTALL MAIN BONDING JUMPER
4) NEED PANEL DIRECTORY
5) HAVE #14 WIRE ON 20 AMP BREAKERS
6) REINSTALL WIRING SO DEAD FRONT CAN BE INSTALLED PROPERLY
7) MARK "SERVICE DISCONNECT"
8) SECURE PANEL TO BLDG SURFACE. DO NOT USE PLASTIC ANCHORS
9) IT APPEARS NEUTRAL BUS HAS BEEN MOVED OR MODIFIED. PLEASE EXPLAIN
10) RESCHEDULE WHEN 100 PERCENT COMPLETE