Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/15/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/14/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) STILL MISSING MAIN BONDING JUMPER |
|
| 04/12/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PREVIOUS INSPECTION REPORT TO BE ON SITE 2) TEP ON SITE MARKING UNDERGROUND FOR NEW SERVICE TO HOME, NEED TO EXPLAIN |
|
| 04/09/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL GROUND RODS 2) INSTALL BREAKERS LISTED FOR USE IN PANEL 3) INSTALL MAIN BONDING JUMPER 4) NEED PANEL DIRECTORY 5) HAVE #14 WIRE ON 20 AMP BREAKERS 6) REINSTALL WIRING SO DEAD FRONT CAN BE INSTALLED PROPERLY 7) MARK "SERVICE DISCONNECT" 8) SECURE PANEL TO BLDG SURFACE. DO NOT USE PLASTIC ANCHORS 9) IT APPEARS NEUTRAL BUS HAS BEEN MOVED OR MODIFIED. PLEASE EXPLAIN 10) RESCHEDULE WHEN 100 PERCENT COMPLETE |