Permit: T10EL00729

Parcel: 136213720


Addresses:

3112 S MARVIN AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/12/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/07/2010 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED BY CONTRACTOR
04/05/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HAVE OPEN SPLICE AT FLOOD LIGHT DRIVE WAY
2) WIRING TO FLOOD LIGHT NOT CODE COMPLIANT, INSTALL PER CODE OR REMOVE
3) RECEPT IN CARPORT TO BE GFI PROTECTED AND HAVE WEATHER PROOF COVER, WIRING IN CARPORT TO BE PROTECTED FROM PHYSICAL DAMAGE
4) OUTDOOR RECEPTS TO BE GFI PROTECTED
5) VERIFY PERMIT FOR PANEL REPLACEMENT
6) REPLACE BROKEN PLATES
7) REPLACE PAINTED OVER RECEPTS
8) INSTALL MAIN BONDING JUMPER IN SERVICE PANEL
9) SEAL OPENING AT SERVICE PANEL WITH NON COMBUSTIBLE MATERIAL
10) RESCHEDULE WHEN COMPLETE