Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T10EL00715

Parcel: 133230960


Addresses:

747 N GRADY AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/12/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/07/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NEED TO REMOVE PIPES FROM TOP OF PANEL THAT IS DEDICATED SPACE 110.27 NEED TO PHASE NEUTRAL 200.6-8