Permit: T10EL00692

Parcel: 140201280

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY POLE

Date Description Inspector Results Comments
04/21/2010 ELECTRIC - TEMPORARY POLE Approved IVRS - Inspection :*
04/19/2010 ELECTRIC - TEMPORARY POLE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) FINISH ITEMS 4 & 7 PREVIOUS
2) TIGHTEN LOOSE TERMINATIONS
04/12/2010 ELECTRIC - TEMPORARY POLE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) UNCOVER UNDERGROUND RACEWAYS, GROUNDS AND GROUND RODS
2) TIGHTEN LOOSE FITTINGS
3) GROUNDING ELECTRODE CONDUCTOR NOT TO BE BONDED TO GROUNDED CONDUCTOR AT SUB PANEL
4) SHEET METAL THREAD SCREWS NOT ALLOWED FOR GROUNDING
5) ABOVE GROUND PVC TO BE SCHEDULE 80 AND SECURED
6) FILL UNUSED OPENINGS IN PEDESTAL
7) SECURE GROUNDING ELECTRODE CONDUCTOR TO PEDESTAL AND STRUCTURE
8) PROTECT CONDUCTORS AT FITTINGS 252.46 & 300.4
9) LABEL BREAKERS AT PEDESTAL
10) CANNOT TRIM CONDUCTOR STRANDS