Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY POLE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/21/2010 | ELECTRIC - TEMPORARY POLE | Approved | IVRS - Inspection :* | |
| 04/19/2010 | ELECTRIC - TEMPORARY POLE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) FINISH ITEMS 4 & 7 PREVIOUS 2) TIGHTEN LOOSE TERMINATIONS |
|
| 04/12/2010 | ELECTRIC - TEMPORARY POLE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) UNCOVER UNDERGROUND RACEWAYS, GROUNDS AND GROUND RODS 2) TIGHTEN LOOSE FITTINGS 3) GROUNDING ELECTRODE CONDUCTOR NOT TO BE BONDED TO GROUNDED CONDUCTOR AT SUB PANEL 4) SHEET METAL THREAD SCREWS NOT ALLOWED FOR GROUNDING 5) ABOVE GROUND PVC TO BE SCHEDULE 80 AND SECURED 6) FILL UNUSED OPENINGS IN PEDESTAL 7) SECURE GROUNDING ELECTRODE CONDUCTOR TO PEDESTAL AND STRUCTURE 8) PROTECT CONDUCTORS AT FITTINGS 252.46 & 300.4 9) LABEL BREAKERS AT PEDESTAL 10) CANNOT TRIM CONDUCTOR STRANDS |