Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) RECALL AFTER FINISH #1,5 & 6 |
|
| 04/13/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SMOKE DETECTORS NEEDED FOR BEDROOMS AND HALL, ALSO INSTALL PER INSTRUCTIONS 2) EXPOSED NM CABLING WIRING-ALSO NOT WIRED TO CODE 3) WROUGHT IRON FOR BEDROOMS TO HAVE QUICK RELEASE 4) GROUNDED RECEPTS ON NON-GROUNDED CIRCUITS 5) BOXES MORE THAN 1/4" BOX TO SURFACE NEED APPROVED ARC SHIELDS 6) BATHROOM RECEPTS TO BE GFCI PROTECTED-NOT IN LIGHT FIXTURES 7) COOLER SWITCH WIRING HANGING OUT OF WALL 8) EXPOSED CONDUCTOR AT BACK PORCH 9) PLEASE VERIFY PERMITS FOR A/C UNIT |