Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/22/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) CALL FOR FINAL AFTER TIE IN |
|
| 03/30/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) A LISTED MAST BRACE KIT IS NEEDED 2) A 2ND GROUND ROD IS NEEDED 3) SUPPORT RISER TO STRUCTURE BELOW ROOF LINE 4) RECEPT COVER TO BE WEATHER PROOF, WHETHER OR NOT PLUGGED INTO AND TIGHT LOCK NUT 5) NEED PERMANENT METAL ADRESS LABEL ON PANEL 6) UNDER TO BE 18" IN DEPTH 7) CLEAN SURFACE UNDER GAS CLAMP |