Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10EL00686
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/07/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
03/30/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE K.O. PLUGS IN ELECTRIC BOXES AS NEEDED 2) RECEPT BOXES AND CONDUIT NOT INSTALLED (SUPPORTED) CORRECTLY AT CEILING IN SHOP AREA (HANING FROM WIRE) 3) RECEPT BOX CONNECTOR BROKEN, BOX HANGING BY WIRE 4) SERVICE PANEL NOT PROPERLY LABELED 5) CONDUIT IN SHOP AREA CEILING NOT PROPERLY SUPPORTED |