Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/21/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/16/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL PROPER COVER ON SERVICE PANEL 2) INSTALL MURRAY BREAKERS IN MURRAY PANEL 3) SWITCH NEUTRALS AND GROUNDS IN SUB PANEL 4) INSTALL #8 GREEN FROM SERVICE PANEL TO SUB PANEL 5) INSTALL PROCTECTIVE PLASTIC BUSHING ON SUB PANEL FEED 6) ALL JACKETS ON NM CABLE TO ENTER INTO ENCLOSURE 1/4" THEN FIRE STOP OPENING IN TOP OF PANEL |
|
| 04/14/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) WORK IS NOT MINIMUM NEC STANDARD FOR CODE 2) PAY REINSPECTION FEE BEFORE NEXT INSPECTION 3) GENERAL CONTRACTORS LICENSE DOES NOT COVER ELECTRICAL WORK |
|
| 04/12/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED |
|
| 04/09/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) NEED CORRECT DEAD FRONT NOT HOMEMADE 2) VERIFY GROUNDING ELECTRODE CONDUCTOR 3) FILL UNUSED OPENING IN MAIN SERVICE 4) SUB PANEL STILL NOT TO CODE 5) WE NOW HAVE A NEW WATER HEATER ON SITE-PLEASE VERIFY PERMIT 6) WHO IS QUALIFIED ELECTRICIAN ? 7) A REFEE MAY BE ASSESSED |
|
| 03/29/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) MISSING DEAD FRONT FOR PANEL AND FILL UNUSED OPENINGS 2) MULTIPULE CONDUCTORS AT BREAKER 3) USE CORRECT SIZE CONDUCTORS FOR BREAKER AMPACITY 4) EXPOSED NM CABLE AT BACK PORCH 5) SUB PANEL NOT TO CODE 6) PLEASE VERIFY REWIRE OF STRUCTURE AFTER 11/05/05 AS STAMPED ON NM CABLE 7) NEED SMOKE DETECTORS IN HALL AND BEDROOMS 8) CONNECTOR NEEDED AT HOOD 9) EXPOSED CABLES ON ROOF |