Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/20/2010 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 04/16/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED PLASTIC BUSING ON #4 OR LARGER 300 2-F 2) NEED TO CLEAN OR SCRAPE PAINT OFF ON GROUND LUG 250.12 |
|
| 04/15/2010 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) SERVICE, GROUNDING AND BONDING ALL OK 2) CALL BACK FOR FINAL |