Permit: T10EL00657

Parcel: 13421089A


Addresses:

7026 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T10EL00657

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/16/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/14/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GROUNDING ELECTRODE CONDUCTOR TO BE CONTINOUS WITH OUT SPLICE
2) BOND GAS PIPE ON HOUSE SIDE OF METER
3) WATER BOND TO BE SIZED PER NEC 250.10 & 250.66
4) NEED 2 GROUND RODS
5) SEAL OPEN KNOCKOUTS IN PANELS
6) RESCHEDULE WHEN COMPLETE
03/25/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HAVE CUT FLEX WITH EXPOSED WIRES INSIDE FLEX
2) INSTALL COVER ON OPEN JUNCTION BOX
3) SEAL OPEN KNOCKOUTS IN BOXES
4) OPEN/DAMAGED SWITCH BOX
5) CRUSHED/DAMAGED EMT
6) HANGING EMT
7) EXPOSED WIRING
8) SEAL OPEN BREAKER POSITIONS IN PANEL
9) BATHROOM RECEPTS TO BE GFI PROTECTED
10) GROUNDING ELECTRODE CONDUCTOR CUT AND REMOVED INSTALL/REPAIR GROUNDING ELECTRODE SYSTEM
11) BOND GAS AND WATER PIPING
12) PROVIDE ACCESS TO ROOF
13) LIGHT FIXTURE FALLING OF BLDG AT REAR
14) OBTAIN SERVICES OF ELECTRICAL CONTRACTOR TO MAKE REPAIRS AND GO THRU SPACE & CHECK ELECTRICAL SYSTEM AND MAKE REPAIRS AS NECESSARY