Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10EL00657
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/16/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/14/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUNDING ELECTRODE CONDUCTOR TO BE CONTINOUS WITH OUT SPLICE 2) BOND GAS PIPE ON HOUSE SIDE OF METER 3) WATER BOND TO BE SIZED PER NEC 250.10 & 250.66 4) NEED 2 GROUND RODS 5) SEAL OPEN KNOCKOUTS IN PANELS 6) RESCHEDULE WHEN COMPLETE |
|
03/25/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) HAVE CUT FLEX WITH EXPOSED WIRES INSIDE FLEX 2) INSTALL COVER ON OPEN JUNCTION BOX 3) SEAL OPEN KNOCKOUTS IN BOXES 4) OPEN/DAMAGED SWITCH BOX 5) CRUSHED/DAMAGED EMT 6) HANGING EMT 7) EXPOSED WIRING 8) SEAL OPEN BREAKER POSITIONS IN PANEL 9) BATHROOM RECEPTS TO BE GFI PROTECTED 10) GROUNDING ELECTRODE CONDUCTOR CUT AND REMOVED INSTALL/REPAIR GROUNDING ELECTRODE SYSTEM 11) BOND GAS AND WATER PIPING 12) PROVIDE ACCESS TO ROOF 13) LIGHT FIXTURE FALLING OF BLDG AT REAR 14) OBTAIN SERVICES OF ELECTRICAL CONTRACTOR TO MAKE REPAIRS AND GO THRU SPACE & CHECK ELECTRICAL SYSTEM AND MAKE REPAIRS AS NECESSARY |