Permit: T10EL00653

Parcel: 107131810

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
04/05/2010 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
03/30/2010 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) CONDUCTOR TO BE INSTALLED IN RACEWAY-BACK OF PANEL NOT THRU BLOCK
2) #8 AND LARGER CONDUCTORS TO BE STRANDED 310.3
3) #8 NM CABLE BREAKER AMPACITY TO BE PER 334.80
4) GROUNDING EQUIPMENT CONDUCTOR TO BE GREEN ENTIRE LENGTH 250.119
5) PLEASE PROVIDE ACCESS TO JUNCTION BOX ABOVE PANEL AND SUB PANELS