Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/05/2010 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 03/30/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) CONDUCTOR TO BE INSTALLED IN RACEWAY-BACK OF PANEL NOT THRU BLOCK 2) #8 AND LARGER CONDUCTORS TO BE STRANDED 310.3 3) #8 NM CABLE BREAKER AMPACITY TO BE PER 334.80 4) GROUNDING EQUIPMENT CONDUCTOR TO BE GREEN ENTIRE LENGTH 250.119 5) PLEASE PROVIDE ACCESS TO JUNCTION BOX ABOVE PANEL AND SUB PANELS |