Permit: T10EL00649

Parcel: 12002189A


Addresses:

4010 S 12TH AV #01

Inspection Status: Denied

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
04/25/2012 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEPERATE GROUNDS AND NEUTRAL AT SUB PANEL
2) CLEAN EXCESS FOREIGN MATERIAL AND DIRT FROM BOTTOM OF SUB PANEL
3) BREAKER NOT SIZED PER CONDUCTOR AMPACITY
4) PLEASE VERIFY LOAD FOR FEEDER CONDUCTOR #8 NM
5) PLEASE VERIFY GROUNDING IN GUTTER ABOVE OUTSIDE PANEL AND MAKE UP
6) NO PAPEROWRK FROM LAST INSPECTION
04/29/2010 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*